The estimation formula can be further simplified for PROFIBUS PA. Data is transferred at a fixed bit rate of 31.25 kBit/s and we can assume that for every process value (PV) 5 bytes are transferred. The time required to transfer such a process value therefore lies approximately around 1.1 ms ( = 5x8 bits).

 

Depending on the coupler used, other bus parameters must be adjusted, slightly altering the calculation.  

 

For a bit rate = 45.45 kBit/s the following applies:

TBCycle 21.3 + (14.5 * slaves) + (1.1 * PV) ms

 

For a bit rate = 93.75 kBit/s the following applies:

TBCycle 29.5 + (11.5 * slaves) + (1.1 * PV) ms

 

These estimation formulae are relatively accurate in practical measurements, as long as no further master is added and no acyclic data is transferred. An acyclic service will, as a rule, require between 40 and 60 ms.

 