Socket |
Male plug |
M12-5 B-coded
according to IEC 60947-5-2 or IEC 61076-2-101
There must be no possibility of confusing the B-coded M12-5 plug with the A-coded plugs of signal lines. |
Pin no. |
Signal |
Function |
|
1 |
VP |
+5V supply for bus termination |
Mandatory |
2 |
RxD/TxD-N |
Data line minus (A conductor) |
Mandatory |
3 |
DGND |
Data ground |
Mandatory |
4 |
RxD/TxD-P |
Data line plus (B conductor) |
Mandatory |
5 |
-- |
not used |
|
Thread |
Shield |
Frame ground connection |
Advisable |
The two conductors in the cable transmit the signals: “Data line plus” (B conductor) and “Data line minus” (A conductor). They are coloured red or green and must not be confused.
The shield must be applied to a large surface at both cable ends. For connection of the shielding it is advisable to use the plug's screw joint. In current versions of the standards, pin 5 is no longer connected to the shield.